We specialize in water pump controller and accessories production.


SL-T21

This product is primarily designed for the protection and control of a directly started single- phase sewage lifting pump .



Email: amy@leading-china.com

Email: kitty@leading-china.com

Email: tina@leading-china.com

+
  • undefined

Product Details


To avoid personal injury or product damage caused by improper operation , please read the product manual carefully before operating or using this product. Operation should only commence after a detailed understanding of the product has been obtained.

This product is primarily designed for the protection and control of a directly started single- phase sewage lifting pump . It provides protection functions such as under voltage , over voltage , dry running , overload , and locked rotor during both manual and automatic control modes . Equipped with a high-level alarm float switch interface , it supports automatic control via float switches or pneumatic sensors .

 

 

 Attention: In case of thunderstorm , please be sure to turn off the power.

Warning

Please strictly follow the instructions for correct installation and use . If the following situations occur, the company will not bear any property loss and legal liability for any failure or loss .

1 . Self-assembled or modified controller.

2 . Controller failure or damage caused by severe weather such as thunderstorms .

3. Use a generator as input power.

4 . When the controller shuts down due to protective action , it is forced to run without manual troubleshooting.

5. The controller cannot work normally due to power outages .

In order to better protect personal and equipment safety, please read the following warnings carefully:

1 . The controller does not have leakage protection function .

2 . The controller must be installed away from the inverter.

3. The liquid level detection line cannot be passed through a metal pipe , and cannot be passed  through the same pipeline with the strong power cable . At the same time , the spacing between  strong and weak power wiring is not less than 30cm .

Due to unlicensed operation or non-standard construction , installation is not carried out in accordance with the requirements of our company's product manual , resulting  in the failure of the controller to work properly. Any losses caused , our company is not responsible and does not bear any legal liability and economic expenses!

 

This product is suitable for normal working environment , avoid installation in the following environment:

 

Technology parameter

  • Rated output power: Single-phase 0 .37 - 2 .2kW (as per the machine nameplate )
  • Rated working voltage: Single-phase AC 220V/50Hz (as per the machine nameplate )
  • Dry run protection action time: Default value 6 seconds , adjustable from 1 to 20 seconds
  • Dry run protection recovery time: Default value 10 minutes , adjustable from 1 to 15 minutes
  • Overcurrent action time: 5 - 150 seconds ( inverse time characteristic - the greater the current , the shorter the action time)
  • Overcurrent fault recovery time: Default value 5 minutes , adjustable from 1 to 10 minutes
  • Stall action time: Less than 0. 15 seconds
  • Short circuit action time: Less than 0. 15 seconds
  • Trip voltage of under voltage:Below the rated voltage by 80% , adjustable from 170 to 200V
  • Trip voltage of over voltage: Above the rated voltage by 115% , adjustable from 240 to 280V
  • Under-voltage and over-voltage action time: Default value 6 seconds , adjustable from 2 to 100 seconds
  • Under-voltage and over-voltage recovery time: Default value 2 minutes , adjustable from 1 to 10 minutes
  • Liquid level transmission distance: 1000 meters
  • RS485 transmission distance: 1200 meters (twisted shielded cable SIP-120 Ω )

 

PRODUCT FEATURE

  • IP65 level of protection grade
  • Touch LCD screen for dynamic real-time display, with automatic screen-off energy saving
  • Dynamic sound and light alarm for faults
  • Power failure memory and power recovery function in automatic mode
  • Automatic setting function for current protection parameters
  • Multi-functional protection (dry run , over current , pump stalled , over voltage , under voltage , short circuit , etc . )
  • Delayed start function
  • Delayed stop function
  • Frequent start protection
  • Ultra-high water level sound and light alarm , automatic dual-pump activation
  • RS485 communication
  • Remote monitoring (optional)
  • Pump rust-proof jog function; configurable inspection cycle and jog operation duration
  • Enable function; can disable any one pump from operation
  • Query of the last 10 faults
  • Ultra-high water level delayed pump stop function (air pressure controller)
  • Real-time liquid level depth display with liquid level compensation function (air pressure controller)
  • Automatic verification of liquid level setting rationality (air pressure controller)
  • Compatible with float control mode; can switch to float control mode (air pressure controller)
  • Regular emptying function; configurable emptying cycle and emptying operation duration (air pressure controller)

 

TROUBLE SHOOTING GUIDE

Fault message on LCD screen

Posible cause

Solutions

The water pump and power

supply are normal , but an

over current protection

occurs immediately upon

startup .

Incorrect setting , motor power exceeding the

controller's rated power, pump overload

Carry out parameter setting or parameter tuning

No response after power-on .

Abnormal power supply or abnormal wiring.

Check the power supply or wiring.

"OFF/ON" button turns

gray in color and cannot

be clicked to start the

water pump .

The controller is in

automatic mode or The single pump mode has been enabled

Switch to manual mode or cancel  the single pump mode and change to the dual pump mode

Appear “ DRY RUN ”

The liquid level in the sewage tank is lower than that of the pump . The impeller is

submerged in water.

The controller will stop the pump or wait for 10 minutes before

automatically restoring it. ( Default duration)

Appear “ OVER LORD ”

Pump over load

protection caused by impeller stuck ,foreign matter, etc .

The controller stops the pump or waits 5 minutes for automatic

recovery.

Appear “ PUMP  STALLED ”

The pump is severely over load or stalled

Check whether the impeller of the pump is stuck or if the power is

mismatched.

Appear “ UNDER V ”

Low voltage causes protection

The controller recovers

automatically after 2 minutes

Appear “ OVER V ”

High voltage causes protection

The controller recovers

automatically after 2 minutes

Fault message on

LCD screen

Posible cause

Solutions

Appear “Pump Failure ”

The water pump is not

connected or is damaged

Connect the water pump or replace the water pump

Appear“ Float Failure ”

Float abnormality or stuck

Replace or reset the float switch position .