We specialize in water pump controller and accessories production.
SLE21
The controller is useful in all cases we need to control and protect single pump managing its turn-on and turn off by different electric installations.
Category:
Product Details
Applications
Protection and control of sewage pumps.
Main features
With open phase,stalled,over current,Dry run,Over/under voltage protection function on Both manual and auto mode. It can realize automatic control by liquid level float balls or air pressure
sensors.
Technology parameter:
- Rated Output Power: 0.37-2 .2 kW ( Refer to the nameplate )
- Rated Operating Voltage: AC220V ( Refer to the nameplate )
- Trip response time of over current: 5 sec-5 min ( Inverse time characteristic - the higher the current , the shorter the time)
- Recovery time of under / over voltage: 2min
- Trip response time of pump stalled: <0. 1 seconds
- Trip response time of over voltage:< 6sec
- Trip response time of under voltage:< 15sec
- Trip voltage of over voltage: 115% of rated input voltage
- Trip voltage of under voltage: 80% of rated input voltage
- Dry-Run Protection Trip Time: 30 seconds
- Over current Fault Recovery Time: 1 minute
- Dry-Run Fault Recovery Time: 1 minute
- Trip response time of short circuit: <0. 1sec
- Liquid level transfer distance: ≤ 1000m
- Degree of protection: IP65
- RS485 transmission distance: within 1200 meters ( using twisted-pair shielded cable STP-120Ω (for RS485 & CAN) one pair 20 AWG)
- Attention: In case of thunderstorm,please be sure to turn off the power.
Open phase only support in three phase model
This product is suitable for normal working environment , avoid installation in the following environment:

TROUBLE SHOOTING GUIDE