We offers a wide range of pump control panel & pump control accessories for the pump control and protection market.
K531
Automatic stops the pump in the case of water shortage, protecting it from dry running without installing float switch or liquid probe in the well
Category:
keyword:
Clamp
Product Details
Features
- Built In function switch
applied for water supply by liquid level control through float switch or liquid probe
applied for water supply by pressure control through pressure switch and pressure tank
applied for drainage by liquid level control through float switch or liquid probe
applied for sewage pump with piggy-back float switch
- Double pumps control
main pump / standby pump automatically alternate
main pump / standby pump automatically switch against malfunctions
standby pump participate running if required
- Automatic stops the pump in the case of water shortage, protecting it from dry running without installing float switch or liquid probe in the well
- Auto / Manual switch
- Dynamic LCD displaying pump running state
- Protect the pump against many faults
- Push Button Calibration
- Pump Accumulative Running Time Displaying
- Pump Last Five Fault Record Displaying
- Starts and stops the pump in accordance with the different liquid level or pressure setting
Technical parameter
Main technical characteristic |
|
Control characteristic |
double liquid levelcontrol |
pressure control |
|
Control method |
Manual /Auto |
Liquid level control characteristic |
pulse electrode probe & float switch |
Pressure control characteristic |
pressure switch (n/c) & pressuretank |
Main technical data |
|
Rated outputpower |
refer to the nameplate |
Rated input voltage |
refer to the nameplate |
Trip response time of overload |
5sec-5min |
Trip response time of openphase |
<2sec |
Trip response time of short circuit |
<0.1sec |
Trip response time ofunder / over voltage |
<5sec |
Trip response time of dryrun |
6sec |
Recovery time of over load |
30min |
Recovery time of under / over voltage/threephase unbalance |
5min |
Recovery time of dry run |
30min |
Trip voltage of over voltage |
115% of rated input voltage |
Trip voltage of under voltage |
80% of rated input voltage |
Liquid level transfer distance |
≤1000m |
Protection function |
Dry run Over voltage Over load Open phase Transient surge Pump stalled Under voltage Short circuit repeat start |
Main installationdata |
|
Working temperature |
-25℃-- +55℃ |
Working humidity |
20% -90%RH |
Degree of protection |
IP54 |
Installposition |
Vertical |
Trouble shooting guide
Fault Message |
Possible Cause |
Solutions |
flashing of |
the real running voltage is lower than the calibrated voltage, pump is in under voltage protection state |
report lowline voltage to the power supply company |
controller will attempt to restart the pump every 5minutes untilline voltage is restored to normal |
||
flashing of |
the realrunning voltage is higher than the calibrated voltage, pump is in over voltage protection state |
report highline voltage to the power supply company |
controller will attempt to restartthe pump every 5minutes untilline voltage is restored to normal |
||
flashing of |
the real running ampere is higher than the calibrated running ampere, pump is in over load protection state |
controller will attempt to restart the pump every 30minutes until running ampere is restored to normal |
pump impeller is jammed / pump motor dragging /pump bearing broken |
check pump impeller orbearing |
|
flashing of |
power supply lose phase |
report to the power supply company |
controller inlet wire or pump cable broken |
repair inlet wire or pump cable |
|
flashing of |
parameter calibration not completed |
refer to parameter calibration setting |
flashing of |
liquid level in the well / sump is below the pump intake,pump stops running |
controller will attempt to restart the pump every 30minutes until liquid level above the pump intake |
flashing of |
pump motor running ampere increasing was greater than the normal running ampere(calibrated ampere)by more than 200%1111 |
cut off power supply&repair or replace pump immediately |
|
no communication link between SC / computer and controller |
connecting the controller to SC /computer to realizelong distance monitoring |
Installation
Electrical connection to the power supply line and electrical pump
- DANGER Electric shock risk
Before carrying out any installation or maintenance operation, the controller should be disconnected from the power supply and one should wait at least 2 minutes before opening the appliance.
- Never connect AC power to output UV W terminals.
- Don't put wire, metal bar filaments etc into the controller.
- Ensure the motor, controller and power specifications matching.
- The electrical and hydraulic connections must be carried out by competent, skilled, qualified personnel.