We offers a wide range of pump control panel & pump control accessories for the pump control and protection market.


K531

Automatic stops the pump in the case of water shortage, protecting it from dry running without installing float switch or liquid probe in the well


keyword:

Clamp


Email: design@cesite.cn

Inquire
+
  • undefined

Product Details


Features

  • Built In function switch

 applied for water supply by liquid level control through float switch or liquid probe

 applied for water supply by pressure control through pressure switch and pressure tank

 applied for drainage by liquid level control through float switch or liquid probe

 applied for sewage pump with piggy-back float switch

  • Double pumps control

  main pump / standby pump automatically alternate

  main pump / standby pump automatically switch against malfunctions

  standby pump participate running if required

  • Automatic stops the pump in the case of water shortage, protecting it from dry running without installing float switch or liquid probe in the well
  • Auto / Manual switch
  • Dynamic LCD displaying pump running state
  • Protect the pump against many faults
  • Push Button Calibration
  • Pump Accumulative Running Time Displaying
  • Pump Last Five Fault Record Displaying
  • Starts and stops the pump in accordance with the different liquid level or pressure setting

 

Technical parameter

Main technical characteristic

Control characteristic

double liquid levelcontrol

pressure control

Control method

Manual /Auto

Liquid level control characteristic

pulse electrode probe & float switch

Pressure control characteristic

pressure switch (n/c) & pressuretank

Main technical data

Rated outputpower

refer to the nameplate

Rated input voltage

refer to the nameplate

Trip response time of overload

5sec-5min

Trip response time of openphase

<2sec

Trip response time of short circuit

<0.1sec

Trip response time ofunder / over voltage

<5sec

Trip response time of dryrun

6sec

Recovery time of over load

30min

Recovery time of under / over voltage/threephase unbalance

5min

Recovery time of dry run

30min

Trip voltage of over voltage

115% of rated input voltage

Trip voltage of under voltage

80% of rated input voltage

Liquid level transfer distance

≤1000m

 

Protection function

Dry run    Over voltage

Over load   Open phase 

Transient surge   Pump stalled 

Under voltage    Short circuit

repeat start

Main installationdata

Working temperature

-25℃-- +55℃

Working humidity

20% -90%RH

Degree of protection

IP54

Installposition

Vertical

 

Trouble shooting guide

Fault Message

Possible Cause

Solutions

flashing of 

the real running voltage is lower than the calibrated voltage, pump is in under voltage protection state

report lowline voltage to the power supply company

controller will attempt to restart the pump every 5minutes untilline voltage is restored to normal

flashing of

the realrunning voltage is higher than the calibrated voltage, pump is in over voltage protection state

report highline voltage to the power supply company

controller will attempt to restartthe pump every 5minutes untilline voltage is restored to normal

flashing of

the real running ampere is higher than the calibrated running ampere, pump is in over load protection state

controller will attempt to restart the pump every 30minutes until running ampere is restored to normal

pump impeller is jammed / pump motor dragging /pump bearing broken

check pump impeller orbearing

flashing of

power supply lose phase

report to the power supply company

controller inlet wire or pump cable broken

repair inlet wire or pump cable

flashing of

parameter calibration not completed

refer to parameter calibration setting

flashing of

liquid level in the well / sump is below the pump intake,pump stops running

controller will attempt to restart the pump every 30minutes until liquid level above the pump intake

flashing of

pump motor running ampere increasing was greater than the normal running ampere(calibrated ampere)by more than 200%1111

cut off power supply&repair or replace pump immediately

no communication link between SC / computer and controller

connecting the controller to SC /computer to realizelong distance monitoring

 

 

Installation

Electrical connection to the power supply line and electrical pump

  • DANGER Electric shock risk

 Before carrying out any installation or maintenance operation, the controller should be disconnected from the power supply and one should wait at least 2 minutes before opening the appliance.

  • Never connect AC power to output UV W terminals.
  • Don't put wire, metal bar filaments etc into the controller.
  • Ensure the motor, controller and power specifications matching.
  • The electrical and hydraulic connections must be carried out by competent, skilled, qualified personnel.

 