We offers a wide range of pump control panel & pump control accessories for the pump control and protection market.
K532
Automatic stops the pump in the case of water shortage, protecting it from dry running without installing float switch or liquid probe in the well
Category:
keyword:
Clamp
Product Details
Features
- Built In function switch to apply different application
applied for water supply by liquid level control
applied for booster by pressure control
applied for water drainage by liquid level control
applied for sewage pump with piggy-back float switch
- Double pumps control
main pump / standby pump automatically alternate
main pump / standby pump automatically switch against malfunctions
standby pump participate running if required
- Automatic stops the pump in the case of water shortage, protecting it from dry running without installing float switch or liquid probe in the well
- Auto / Manual Switch
- Protect the pump against many faults
- Dynamic LCD displays pump running information
- Pump accumulative running time displaying
- Pump last five fault record displaying
- A/B pump operation enable or disable function
- Starts and stops the pumps in accordance with the different liquid level or pressure setting
- Pump shaft anti rust
- Pump start time delay (Time settable)
- Pump stop time delay (Time settable)
Technical parameter
Main technical characteristic |
|
Control characteristic |
double liquid levelcontrol |
pressure control |
|
Control method |
Manual /Auto |
Liquid level control characteristic |
pulse electrode probe & float switch |
Pressure control characteristic |
pressure switch (n/c) & pressuretank |
Main technical data |
|
Rated outputpower |
refer to the nameplate |
Rated input voltage |
refer to the nameplate |
Trip response time of overload |
5sec-5min |
Trip response time of openphase |
<2sec |
Trip response time of short circuit |
<0.1sec |
Trip response time ofunder / over voltage |
<5sec |
Trip response time of dryrun |
6sec |
Recovery time of over load |
5min |
Recovery time of under / over voltage/threephase unbalance |
2min |
Recovery time of dry run |
30min |
Trip voltage of over voltage |
115% of rated input voltage |
Trip voltage of under voltage |
80% of rated input voltage |
Liquid level transfer distance |
≤1000m |
Protection function |
Dryrun Over load Undervoltage Over voltage Openphase Pump stalled Pump shaft rustprotection |
Main installationdata |
|
Working temperature |
-25℃-- +55℃ |
Working humidity |
20% -90%RH |
Degree of protection |
IP22 |
Installposition |
Vertical |
Trouble shooting guide
Fault Message |
Possible Cause |
Solutions |
flashing of |
the real running voltage is lower than the calibrated voltage, pump is in under voltage protection state |
report lowline voltage to the power supply company |
controller will attempt to restart the pump every 5minutes untilline voltage is restored to normal |
||
flashing of |
the realrunning voltage is higher than the calibrated voltage, pump is in over voltage protection state |
report highline voltage to the power supply company |
controller will attempt to restartthe pump every 5minutes untilline voltage is restored to normal |
||
flashing of |
pump motor running ampere increasing was greater than the normal running ampere(calibrated ampere)by more than 200% |
cut off power supply&repair or replace pump immediately |
flashing of |
the real running ampere is higher than the calibrated running ampere, pump is in over load protection state |
controller will attempt to restart the pump every 30minutes until running ampere is restored to normal |
pump impeller is jammed / pump motor dragging /pump bearing broken |
check pump impeller orbearing |
|
flashing of |
power supply lose phase |
report to thepower supply company |
controller inlet wire or pump cable broken |
repair inlet wire or pump cable |
|
flashing of |
parameter calibration not completed |
refer to parameter calibration setting |
flashing of |
liquid level in the well / sump is below the pump intake,pump stops running |
controller will attempt to restart the pump every 30minutes until liquid level above the pump intake |
|
no communication link between SC / computer and controller |
connecting the controller to SC /computer to realizelong distance monitoring |
Installation
Electrical connection to the power supply line and water electrical pump
Three phase input and output wiring